Wireless sensors are arriving on plant floors, and the security review usually opens with one question: which Purdue level do they belong on? The Purdue Model gives operational technology (OT) teams a shared map of where systems live and which networks may talk to each other. But the Purdue Model OT teams rely on was drawn in 1992 for wired, deterministic control systems. A battery-powered temperature sensor, a gateway with a cellular uplink or a LoRaWAN network covering a whole campus doesn’t sit neatly on one level.

Below are the Purdue levels, an answer on whether the model still holds up, and where capture hardware fits on it. The last sections cover securing that hardware with IEC 62443 zones and conduits, which matters more than the level a diagram assigns it.

What the Purdue Model for ICS Security Actually Is

The Purdue Model comes from the Purdue Enterprise Reference Architecture, which Theodore Williams and an industry consortium at Purdue University published in the early 1990s. Its first job was to describe how information moves through a manufacturing enterprise, from the physical process up to business planning. Security teams adopted it later to separate industrial control systems (ICS) from corporate IT. The U.S. Department of Energy’s Purdue framework paper covers that history and how critical infrastructure uses the model today.

The Purdue Model Levels, 0 Through 5

Each level groups systems by function. The lower the level, the closer it sits to the physical process and the tighter its timing.

  • Physical process (Level 0): sensors, actuators, motors and valves that touch the process directly.
  • Basic control (Level 1): programmable logic controllers (PLCs), remote terminal units (RTUs) and safety systems that read Level 0 and drive it.
  • Area supervisory control (Level 2): human-machine interfaces (HMIs), SCADA and the operator workstations that watch a line or area.
  • Site operations (Level 3): historians, manufacturing execution systems (MES) and site-wide control services.
  • Industrial DMZ (Level 3.5): a demilitarized zone (DMZ) that buffers OT from IT. Traffic between Level 4 and Level 3 should cross it rather than pass straight through.
  • Business logistics (Level 4): ERP, scheduling, email and the plant’s business network.
  • Enterprise (Level 5): corporate data centers, cloud services and internet access.

Is the Purdue Model Still Relevant in OT?

Yes, as a shared vocabulary and a map of where systems live. No, as a security control on its own.

The map holds up well. When an engineer says a device sits at Level 2, everyone in the room knows roughly what it does, what it talks to and how much downtime it can tolerate.

The model describes where traffic should flow, though, and it can’t stop traffic that flows somewhere else. Plants have also changed underneath it. Historians, SCADA servers and engineering workstations often run as virtual machines now. A single hypervisor or management console can sit one hop from production. In August 2026, attackers began exploiting a critical VMware vCenter flaw, CVE-2026-59310, five days after Broadcom released the patch (The Hacker News). Labeling those hosts Level 3 on a diagram didn’t change what an attacker could reach through them. Keep the levels for orientation, then secure the architecture you actually run, including the parts the diagram leaves out.

Where Wireless Sensors and Gateways Fit on the Purdue Model

Most Purdue diagrams leave capture hardware off entirely. It has three pieces: sensors on equipment and assets, gateways that collect their signals, and the backhaul that carries data out. Each piece behaves differently, so each needs its own placement.

Purdue Model Levels
Capture Hardware
Level 5Enterprise network, cloud services
Conduit ACellular backhaul to the customer's own cloud
Level 4Business logistics: ERP, scheduling
Level 3.5Industrial DMZ between OT and IT
Level 3Site operations: historian, MES
Conduit BEthernet, Wi-Fi or private 5G to the site historian or broker (MQTT/REST)
Level 2Area supervisory control: HMI, SCADA
Level 1Basic control: PLCs, RTUs, safety systems

Capture zone

  • Wireless sensors on equipment and assets (read-only, outside the control loop)
  • Gateways
  • Backhaul: Ethernet, Wi-Fi, cellular, private 5G, LoRaWAN
Level 0Physical process: sensors, actuators, valves
Capture hardware sits physically beside Levels 0 and 1 but reaches upward through its own defined conduits.

Sensors Behave Like Level 0 Devices but Don’t Talk to PLCs

A wireless sensor clamped to a pump or a tool cart sits physically at Level 0. It measures temperature, vibration, location, or whether a machine is on, off or idle. Unlike a traditional field instrument, it isn’t wired into the control loop. It takes no commands from a PLC, and the PLC doesn’t need its readings to run the process.

That difference changes the risk. A compromised field instrument can change how a process behaves. A read-only sensor outside the control loop can report bad data, but it has no path to actuate anything. Place it at Level 0 on the floor plan and treat it as a separate, lower-consequence asset in security planning.

Gateways and Backhaul Cross Levels by Design

Gateways are harder to place. A gateway sits on the floor near Level 0 and 1 devices, yet its whole job is to move data up and out. The backhaul it uses decides where that data goes next:

  • Wired Ethernet into a plant network segment
  • Wi-Fi on an existing or dedicated network
  • Cellular (4G or 5G), which leaves the plant network entirely
  • Private 5G over CBRS, owned by the site and kept apart from the control network
  • LoRaWAN, a long-range, low-power network that usually reports to its own network server

A gateway on a cellular uplink links Level 0 to Level 5 in one hop. No single Purdue level describes that path, and squeezing it onto one hides the path from the people reviewing it. At Thinaer, the environment decides the tech we deploy, so one site might run several of these at once. For more on that, see how the capture layer works in IT/OT convergence.

Why “Which Level?” Is the Wrong First Question

Ask two other questions first: where does this data flow, and who owns each part of the path? A sensor that reports to a Level 3 historian over a site-owned private 5G network is one conversation. A sensor that reports to a cloud service over a carrier network is another. Once the path and its owner are clear, the level assignment mostly follows, and the security controls attach to that path.

Pairing Purdue With IEC 62443 Zones and Conduits

The ISA/IEC 62443 series, published by the International Society of Automation (ISA) and the International Electrotechnical Commission (IEC), gives capture hardware the security structure Purdue lacks.

A zone is a group of assets that share the same security requirements. A conduit is a defined communication path between zones, with its own rules for what can cross and how. Zones follow trust and consequence, so they don’t have to line up with Purdue levels.

For capture hardware, put sensors, gateways and backhaul in their own capture zone, separate from the control zone where PLCs and HMIs live. Then define the conduits upward: which systems the capture zone may send data to, over which protocols, in which direction. A gateway that spans Level 0 and Level 5 then has one documented conduit, which auditors can check against policy.

Enterprise Zone (Levels 4 and 5)

ERP, business network, the customer's cloud and analytics

Conduit: DMZ to enterprise, brokered and logged

Industrial DMZ (Level 3.5)

Brokers, replicated historian, jump hosts

Conduit: control to DMZ

Control Zone (Levels 1 to 3)

PLCs, HMIs, SCADA, site historian, MES

Conduit: outbound only, MQTT or REST

Capture Zone

Wireless sensors, gateways and backhaul on their own segment

No conduit into the control zone

Purdue still tells you which zones sit near the process and which sit near the business. Zones and conduits define what may move between them.

OT Network Segmentation for Capture Hardware

Zones and conduits only help if the network enforces them. For capture hardware, good OT network segmentation comes down to a handful of decisions, and they apply however your site draws the Purdue Model in OT.

Give capture devices their own segment or VLAN, apart from control traffic. Sensors and gateways shouldn’t share a broadcast domain with PLCs, even when they sit on the same machine.

Keep paths outbound-only wherever you can. Gateways send data to the systems that consume it, and nothing outside the capture zone should need to open a connection into it.

Deliver data over standard protocols such as MQTT and REST. Send it to systems you control, like a historian, a message broker, an MES or a data platform. That keeps the destination inside your security boundary and under your own identity and access management (IAM). We cover how this maps to zero trust in our post on where a capture-layer vendor fits inside a zero trust architecture.

Then document the conduit. Write down where data goes, over what backhaul and in which direction, so your security team can test it at every audit. A wireless deployment without that record will struggle in review, however well the hardware performs.

What This Looks Like in Defense and Classified Environments

Defense Industrial Base (DIB) facilities add rules commercial plants never face, around ordnance areas, classified bays and secure networks. A wireless deployment has to satisfy those rules before anyone asks which Purdue level it sits on.

Thinaer’s capture layer is DISA (Defense Information Systems Agency) approved for defense networks and HERO ZERO certified for use around ordnance. Thinaer also has patent-pending coverage for classified environments, where most wireless platforms can’t deploy at all. Captured data stays inside the customer’s boundary and flows to the systems they choose, under their own IAM. The customer maintains its own compliance posture, and the deployment works within it. Our post on AI in classified environments goes deeper on capture inside the boundary.

Putting Capture Hardware on Your Purdue Diagram

The Purdue Model stays on the OT whiteboard because it gives everyone the same picture of where systems live. Capture hardware needs a deliberate spot on that picture, plus its own zone and documented conduits that say exactly what it can reach. With both in place, the security team reviews wireless sensing against a design it has already seen.

“Purdue is the map. Zones and conduits are the locks.”

Thinaer captures data from equipment and spaces your systems have never recorded, using 50+ sensor types and whatever backhaul your site supports. Sonar gives your team visibility from day one, and the same data flows to any system or model you choose. See how Sonar delivers visibility inside your boundary.

Frequently Asked Questions

What are the levels of the Purdue Model?

Six main levels, 0 through 5, plus a Level 3.5 industrial DMZ. Levels 0 to 3 cover the physical process, control, supervision and site operations. Levels 4 and 5 cover business systems and the enterprise network.

Does IoT fit in the Purdue Model?

Partly. Wireless sensors sit physically at Level 0, but gateways and their backhaul often cross several levels at once. Placing that hardware in its own IEC 62443 zone with defined conduits works better than forcing it onto one level.

What replaced the Purdue Model?

Nothing has replaced it outright. Most OT security programs keep the Purdue Model as the reference map. They add IEC 62443 zones and conduits, plus zero trust principles, to control what moves between systems.